Maintaining Systems that Protect
According to a 2017 National Fire Protection Association (NFPA) report, fire departments respond to 7,400
restaurant and bar fires every year.1 Although the cooking equipment is the leading cause of those
fires, 70% did not spread beyond
the place of fire origin. The NFPA restaurant standard, NFPA 962, requires a kitchen suppression system for the
protection of the cooking appliances and associated hoods and ducts. A logical conclusion is that these kitchen
systems are doing
a good job of protecting employees and patrons and keeping property losses to a minimum.
"Fire departments respond to
7,400 restaurant and bar fires every year...the cooking
equipment is the leading cause of those fires."
According to NFPA 17A3, the inspection, testing, and maintenance (ITM) of commercial kitchen fire
suppression systems is the responsibility of the owner of the system, although the standard allows that
responsibility to be transferred
to a management company or tenant by a written agreement [17A, 8.1.1]. Here is information that can be used to
convince owners and their associates that they should continue to be diligent in their efforts to maintain these
systems in proper
working order to protect people and property.
Monthly Inspections
On a monthly basis, the owner is required to perform an inspection of the kitchen system in accordance with the
owner’s manual [17A, 8.2.1]. This monthly quick-check inspection must include verification of the following items:
- Tamper seals on cylinders are in place and not broken.
- Manual pull stations are appropriately marked and not obstructed.
- The system service tag shows maintenance was performed within the last 6 months.
- There is no obvious physical damage to the fire suppression system.
- There is no condition that might prevent system operation.
- The stored pressure cylinder pressure gauge is in the operable range.
- Nozzle blowoff caps (or foils) are installed on nozzles and undamaged.
- A system service technician has reviewed protection for new cooking appliances or relocation of existing
equipment.
Although this is often called the owner’s inspection, it is permissible for a system service technician to
perform this monthly inspection. This is often preferable as any corrective action that involves maintenance of
the system must be performed
by a trained service technician and can be performed at the time of the inspection [17A, 8.2.3.1].
The system owner is required to keep a copy of the system manufacturer’s installation and maintenance manual or
the owner’s manual in the restaurant and make it available if requested by the authority having jurisdiction [17A,
8.2.1.1]. Records
of monthly inspections must be kept, including the date of inspection, the person performing the inspection, and
any corrective actions taken [17A, 8.2.4]. Those records must be retained for all inspections performed between
semiannual maintenance
service intervals [17A, 8.2.6].
Any work that involves system repair, replacement of parts, or service activities performed to ensure proper
operation of the system is called system maintenance [17A, 3.3.11]. This work is only permitted to be performed by
a service technician
who has a certification and special training on these systems [17A, 8.3.1]. Many states require this training and
certification, in accordance with NFPA 17A, as part of state licensing programs.
Semiannual Maintenance
The maximum interval for performing system maintenance is every 6 months and it must be performed in accordance
with the system manufacturer’s design, installation, and maintenance manual [17A, 8.3.2]. System recharging and
maintenance must also
be performed after any system discharge or if there is insufficient pressure as indicated on the system pressure
gauge. After a system has discharged, the piping must be flushed with clean water and then blown out with dry air
or nitrogen
[17A, 8.4.1].
All restaurant kitchen systems are provided with manual and automatic means of operation. After any maintenance
or recharge, the service technician performs a procedure that places the system in a normal operating condition
that allows either
manual operation of the system with a manual pull station or automatic operation by heat-actuated fusible links.
For these systems to remain reliable and operable in the event of a fire, the fusible links are required to be
replaced during
the 6-month maintenance of the system [17A, 8.3.4].
The system service tag provides a record of the year of manufacture and the date of installation of the new
fusible links so that the required periodic replacement can be verified by the owner and the authority having
jurisdiction [17A, 8.3.4.2].
All replacement fusible links must be listed and must have the same temperature ratings as the ones being replaced
unless new temperature readings indicate a need for a change [17A, 8.3.4.1]. Fusible links removed during
servicing are destroyed
or discarded so they cannot be used again [17A, 8.3.4].
Periodic Hydrostatic Testing (12-years)
On a 12-year basis, extinguishing agent containers and system hoses are required to undergo a hydrostatic test
[17A, 8.5.1]. This pressure test helps ensure that containers and hoses can withstand normal operating pressures.
No leakage, rupture,
or movement of hose couplings is permitted during testing [17A, 8.5.2.1]. At the time of hydrostatic testing, the
wet chemical extinguishing agent is replaced [17A, 8.5.3]. Only the agent marked on the system agent container is
permitted to
be used for recharging. No substitutes are permitted.
Maintenance Reports
After maintenance is completed, a maintenance report must be provided to the owner including any corrective
actions taken and recommendations [17A, 8.3.3.6]. Maintenance reports are required to be kept for a period of one
year and are subject
to review by the authority having jurisdiction [17A, 8.3.3.6.1].
Service Collars
Similar to portable fire extinguishers, after recharging including hydrostatic testing of cylinders, a service
collar is installed on stored pressure cylinders with the month and year of service indicated with a perforation
using a hand punch
[17A, 8.6.3]. Cartridge-operated containers are not required to have service collars installed [17A, 8.6.4].
The most reliable kitchen systems are those that are inspected, tested, and maintained according to NFPA 17A and
the manufacturer’s manuals. Your customers will appreciate the work you perform to keep their systems
code-compliant and reliable
in the event of a fire emergency.
1“Structure Fires in Eating and Drinking Establishments”, Richard
Campbell, February 2017, National Fire Protection Association
2NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial
Cooking Operations, 2024 Edition
3NFPA 17A, Standard for Wet Chemical Extinguishing Systems, 2024
Edition